Tripp Lite 120/208V Power Supply User Manual


 
3 V
+
-
10
ThisfemaleDB9portconnectsyourUPSviaanRS-232cabletoaworkstationorserverequippedwithTrippLitesoftware.TheportusesRS-232
communicationstoreportUPSstatusandpowerconditions.Usingthisport,TrippLitesoftwarecanmonitorandmanagenetworkpowerand
automaticallysaveopenfilesandshutdownequipmentduringablackout.ContactTrippLiteCustomerSupportat(773)869-1234forinformationon
availableSNMP,networkmanagementandconnectivitysoftwareandproducts.
RS-232signalsandoperationsinclude:loadlevel,batterystatus,batterylevel,operationmode,ACinputvoltage,ACoutputvoltage,ACinput
frequency,temperatureinsideunit,setshut-downdelaytime,enable/disablealarmandremoteshutdown.
Hardware: Pin assignment:
BaudRate: 2400BPS Pin2: TXD(TransmitData)
DataLength: 8bits Pin3: RXD(ReceiveData)
StopBit: 1bit Pin5: GND(SignalGround)
Parity: NONE
ThisfemaleDB9portconnectsyourUPStoanIBMAS-400
computerviaanAS-400cable.TheportusesAS-400communicationsto
reportUPSstatus.ItcanbeusedtoallowanAS-400toautomaticallysave
openfilesandshutdownitsoperatingsystemduringablackout.AS-400
protocolincludes:operationoninverter,operationonACpowersupply,
operation on battery and low battery alarm.
Pin assignment:
Pin5: Common
Pin 6: Operation on AC power supply
Pin7: Lowbatteryalarm
Pin8: Operationoninverter
Pin 9: Operation on battery
AS-400 INTERFACE TABLE
Pin6,5 Pin7,5 Pin8,5 Pin9,5
Battery OFF * ON ON
Low Battery OFF ON ON ON
DirectMainsSupply ON OFF OFF OFF
Inverter OFF * ON *
*Inactive:maybeineitherstate.
DRY CONTACT INTERFACE TABLE
UPS Operating Mode Pin8,3 Pin1,3
Normal OPEN OPEN
Back Up CLOSE *
Low Battery CLOSE CLOSE
*Inactive:maybeineitherstate.
ThisfemaleDB9contact-closureportallowsyourUPStosend
contact-closure signals to indicate that it is on battery back-up mode
and if its batteries are running low. The port can also receive a
remote shutdown signal.
Pin assignment:
6.1 RS-232 Interface
6.2 AS-400 Interface
6.3 Dry Contact Interface
6. Communications