DANGER!
BATTERY CARTRIDGE FUSES MUST BE INSERTED LAST DUE TO THE DANGER OF POTENTIAL
ARCING OF CONNECTORS.
FUSE REPLACEMENT
The fuses protect against short circuit damage. If a heavy overload or short circuit is encountered,
a fuse will blow. A battery pack with a blown fuse will not deliver any output voltage to the UPS
system.
DANGER!
The fuses must be replaced by a qualified electrician. To reduce the risk of fire, replace only with
fuses of the same type or rating (UL-recognized 30A 600VDC rated cartridge fuses).
Useavoltmeter(user-supplied)totestthevoltageofthebatterypack.
Observeproperpolarity:connectthevoltmeter'sBLACK probe to the
batterypack'sBLACKconnector;connectthevoltmeter'sRED probe
tothebatterypack'sREDconnector.Togetaproperreading,make
surethevoltmeter'sprobestouchthemetalcontactsinsidethebattery
pack'sconnectors.The battery pack's Acceptable DC Voltage Range
is between 220 and 280V DC. If several attempts at voltmeter tests
yieldresultsoutsidethisrange,contactTrippLiteforassistancein
determining the possible causes of the incorrect voltage reading.
12
12
Connect the BLUE and WHITE jumper cables on each internal battery
packtoitscorrespondingfuseblock.Seeprintingnexttofuseblockto
locate the correct fuse block for each cable.
10
10
Insert the battery cartridge fuses into each fuse block. The fuses are
identical,andcanbeinsertedintoanyoftheblocks.Makesurethatthe
fuses are firmly snapped into place.
11
11