Tripp Lite 120/208V Power Supply User Manual


 
8
Momentarilypressthe“SELECT”buttononthefrontpaneltobrowsethroughdifferentpowerreadingsontheLCDDisplay.
BYPASS OUTPUT
R: XXXV R: XXX.XV
S: XXXV S: XXX.XV
T: XXXV T: XXX.XV
(Bypass&OutputVoltage)
OUTPUT LOAD
R: XXX% XXX.XA
S: XXX% XXX.XA
T: XXX% XXX.XA
(OutputLoad&Current)
MAINS INVERTER
R: XXXV R: XXX.XV
S: XXXV S: XXX.XV
T: XXXV T: XXX.XV
(Mains&Inverter Voltage)
BYPASS: XX.XHz
MAINS: XX.XHz
OUTPUT: XX.XHz
INVERTER: XX.XHz
(Bypass,Mains,Output&InverterFrequency)
(ChargerMode,Charger/BatteryVoltage&BatteryPercentage)
(SerialNumber,DCBUSVo ltage,Temperature&FirmwareVe rsion)
(ButtonFunctions)
CHARGE FLOATING
CHARGER:XXX.XV
BATTERY: XXX.XV
BATTERY: XXX.X%
SN: XXX
DCBUS: XXV - XXV
TEMP: XXX.X˚C
VERSION: XXX
ON: UPS START
OFF: UPSBYPASS
SEL: UPS MESSAGE
ENT: SET UPS
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
WhileinBypassMode,theUPSmonitorstheinputvoltage,whichonBypassequalstheoutputvoltage.Iftheoutputvoltagepassesoutofanacceptable
range(between15%higherand20%lowerthannominal),theUPSdisplaystheconditiononitsLCDandstopssupplyingoutputpowertoitsload.If
powerlevelsreturntoanacceptablelevel,theUPSresumessupplyingpowertotheload,anditsLCDreportsthatoutputvoltagewastoohighortoolow
atonetime,buthasreturnedtonominal.
Bypass Voltage Condition LCD Display Message
>15%HigherthanNominal BYPASSHINOO/P
>20% Lower than Nominal BYPASSLONOO/P
WasTooHigh,NowNominal BYPASSWASHI
WasTooLow,NowNominal BYPASSWASLO
4.4 LCD Display Select Button
5.1 Operation On Bypass—Voltage Out Of Range
5. Operation
(
Special Conditions
)
4. Operation
(
Normal Conditions
)
(
continued
)