Tripp Lite SU1500XLCD Power Supply User Manual


 
22
Operation
2
The OUTPUT FREQUENCY selection screen will appear.
OUTPUTFREQUENCYreferstothecycles-per-second(Hz)ofUPSoutputpower.Thisvalueis
mostcommonlysettomatchtheprevailingcountryorregion-specificfrequency.Ingeneral,in
theUSA,CanadaandMexicousethe60Hzfactorysetting.In100-127V50Hzlocations,such
asJamaica,AntiguaandpartsofJapan,settheUPSto50Hz.Tosuccessfullyconfigureyour
UPStoconvertfrequencyfrom50-to-60Hzor60-to-50Hz,setBOTHtheOUTPUTFREQUENCY
tothedesiredsettingandenablethisfunctionbysettingtheFREQCONVERSIONtoENABLE.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
60Hz(factory),50Hz
To leave UPS setup mode,
PRESS andHOLD theSETUP
BUTTON (about 3 seconds).
NOTE-theUPSmustbeinSTANDBYMODE
tochangetheoutputfrequencysetting
3
The FREQUENCY CONVERTER selection screen will appear.
FREQUENCYCONVERTERreferstotheabilityoftheUPStoconvert60Hzto50Hzor50Hzto
60Hz.TheUPSsystemautomaticallyselects50Hzor60Hzoperationbasedonutilitypower
conditions at start-up. The factory configuration of OFF is ideal for most applications. Some
usersmaywishtoconvertfrequencyforconnectedequipment.Tosuccessfullyconfigureyour
UPSforfrequencyconversion,turnONtheFREQUENCYCONVERTERfunctionandSETthe
OUTPUTFREQUENCYfunctiontothedesired50or60Hzsetting.
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen , press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
OFF(factory), ON
To leave UPS setup mode,
PRESS andHOLD theSETUP
BUTTON (about 3 seconds).
NOTE-theUPSmustbeinSTANDBYMODE
tochangethefrequencyconvertersetting
4
The BYPASS RANGE selection screen will appear.
BYPASS RANGE: Sets the allowable voltage deviation from nominal input voltage that is
acceptable for the unit to go to bypass in a fault condition. If the voltage goes outside the range,
the unit will not go to bypass. If the unit is already in bypass, it will turn the output off. The factory
settingofWIDEiscompatiblewiththevastmajorityofnetworkingequipment.Regardlessofthe
“plusorminus”valueentered,thehighestbypassvoltageavailableis135V.Thelowestbypass
voltageavailableis90V(fullload)and70V(<70%load).The“Wide”rangereflectsthesesame
values(fullload90to135V/<70%load70to135V).
ACCEPT AND ADVANCE VIEW ALTERNATE SETTINGS LEAVE UPS SETUP MODE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
ToVIEWALTERNATESETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
HI(factory),5%,6%,7%,8%,
9%, 10%, 11%, 12%, 13%,
14%, 15%
To leave UPS setup mode,
PRESSandHOLDtheSETUP
BUTTON (about 3 seconds).