Tripp Lite SU1500XLCD Power Supply User Manual


 
TAP the ON BUTTON during SETUP MODE operation to confirm the
current selection
The LCD screen will advance to the next configuration item.
See the Configuration section for more information
In the setup mode, this button can also be used to confirm the selection.
HOW? TAP the ON BUTTON (less than 1 second)
WHEN? The UPS must be running in SETUP MODE with the SET
icon lighted for the CONFIRM SELECTION input to take
effect.
7
Features
CONFIRM SELECTION
PRESS and HOLD the OFF BUTTON during ONLINE, ECONOMY,
BATTERY, FREQUENCY REGULATION or FREQUENCY CONVERSION
modes
The UPS will immediately report OFF on the LCD screen.
At this point the UPS can be unplugged and placed in storage.
3
OFF BUTTON: : This button offers two main functions
depending on the state of the UPS when it is pressed: TURN
OFF UPS OUTPUT and CLEAR UPS FAULT MODES
HOW? PRESS and HOLD the OFF BUTTON until a BEEP is
heard (about 3 seconds), then RELEASE
WHEN? ? The UPS must be running in ONLINE (shown above),
ECONOMY, BATTERY, FREQUENCY REGULATION or
FREQUENCY CONVERSION MODE for the TURN OFF
UPS OUTPUT function to take effect.
ChangesUPSoperatingmodetoSTANDBY&TURNSOFFUPSOUTPUT
when pressed during ONLINE, ECONOMY, BATTERY, FREQUENCY
REGULATIONandFREQUENCYCONVERSIONMODES
PRESS and HOLD the OFF BUTTON until a BEEP is heard as the
UPS is reporting an ERROR CODE
The error code will be reset and the UPS will return to BYPASS
or STANDBY mode, depending on the FAULT encountered.
HOW? PRESS andHOLD the OFFBUTTON until aBEEP is
heard (about 3 seconds), then RELEASE
WHEN? The UPS must be reporting an ERROR CODE (starting
with “E”) in order for the CLEAR UPS FAULT function to
take effect
ClearsoutUPSSHUTDOWNorFAULTMESSAGINGontheLCDscreen
TURN OFF UPS OUTPUT
CLEAR UPS FAULT MODE
13-03-138 93-3168-EN.indd 7 3/28/2013 1:04:51 PM