Western Telematic RPC-4840N Network Card User Manual


 
2. Password: (Up to 16 Characters) Assigns a User
Password to this circuit. When a User Password is
assigned, the circuit is then "owned" by that password.
When a User Password is entered at login, the user will
have access to only the circuit(s) which are owned by this
password. (Default = undefined).
Notes:
·
If you wish to allow a single user to access both
switched circuits, assign the same User Password
to both circuits.
·
If the System Password is defined, and the circuit's
User Password is not defined, then the System
Password will "own" this circuit, and only the
System Mode will be able to control the circuit.
3. Boot Delay: During a Boot cycle, the circuit is first
switched off and then switched back on. The Boot Delay
is the length of time which elapses between the time when
power is switched off and the time that power is restored.
The Boot Delay can be 1, 5, 10, 15, 30 or 60 seconds.
(Default determined by Option Switch 2; Factory Setting =
5 Seconds).
4. Power-Up Default: Determines how this circuit will react
when the /D (default) command is invoked, or after a
power interruption. Each circuit can be automatically
switched On or Off as specified by the Power-Up Default.
(Default = On).
After Circuit Parameters have been defined, press [Esc] to exit
from the Circuit Parameters menu.