Xantrex Technology GT3.0 Power Supply User Manual


 
Preparing for the Installation
975-0131-01-01 213
Preparing for the Installation
Ensure your local utility is consulted for any requirements for connecting to or
returning power to the grid. Obtain all permits necessary to complete the
installation. Consult your local/national electrical code for more information.
This section includes the following topics:
•“Wiring on page 213
•“Circuit Breakers and Disconnect Switch on page 213
•“Other Materials Needed on page 214
•“Equipment Needed on page 214.
Wiring
Wire size and length will be determined by the location of each component and
their relative distance to each other. Wire sizes may also be affected by whether or
not conduit is used.
Recommended wire
stripping length
Strip all wires 9 mm (3/8 inch).
Acceptable wire
sizes
The AC and DC terminal blocks in the GT Inverter accept wire sizes from
#14 AWG to #6 AWG.
Wiring should be sized such that the maximum voltage drop at full power from
the PV array to the inverter is 2% or less.
Circuit Breakers and Disconnect Switch
The following circuit breakers, disconnect switch and fuse are required for
installing this equipment.
AC Circuit Breaker Requirements
In North America, the main utility service panel must dedicate a double pole
breaker (240 volts AC) to operate each GT Inverter installed. The GT Inverter
requires a 20-Amp breaker.
Important:
In this manual wiring and wires are used in reference to both AC and
DC wiring/cabling and wires/cables.
Important:
Wiring should not be undersized. Undersizing of wiring can result in
significant power losses and reduction in system efficiency.