Fault Mode causes These message screens only appear when there is a fault, and then flash
alternately with the Inverter Offline default screen (Table 5-5) until the fault is
corrected.
Table 5-8
Fault Message Screens
Display Description
When the actual DC voltage is over or under the allowable
range, 165 to 600 Vdc. Self-clearing, no action required.
The PV array should be configured such that DC voltage
does not fall below 195 Vdc or rise above 600 Vdc.*
* It is normal to receive this fault during low light conditions at dawn or dusk. At
such times, the array does not have sufficient energy to power the inverter, so
the PV voltage drops below 165 volts occasionally.
When the actual AC voltage is over or under the allowable
range, as specified in Output on page A2.
This is a utility fault; it will clear itself when the AC voltage
comes within the specified range.
Grid fault. When this fault is cleared the protection timer will begin its
countdown and you will see the Reconnecting in sss seconds and Inverter
Offline special screens (see Table 5-10) flashing alternately until the
countdown is complete.
When the actual Frequency is over or under the allowable
range, as specified in Output on page A2. This is a utility
fault; it will clear itself when the frequency comes within the
specified range.
When the units internal temperature is greater than 80° C
(176° F), the unit will shut down automatically and only
restart when the temperature has dropped to less than 70° C
(158° F).
When a grounding fault is detected. The ground fault fuse
will be blown. The system must be shut down completely,
the fault corrected, the fuse replaced (see Replacing the
Ground Fault Protection Fuse on page 64) and then the
system restarted. Troubleshooting a grounding fault should
be performed by qualified personnel.
Applicable only in German installations.
Appears if the GT Inverter unit has been shut down via a
computer connected to the RS-232 port.
The protection processor is not responding.