8 InfraStruXure System—Installation and Start-Up
Heat Output
Consider the heat dissipation ratings of equipment to determine cooling requirements. Additional
cooling equipment may be required. Heat output of the InfraStruXure PDU is shown below.
Voltage
InfraStruXure PDU with a transformer 208V input 7169 BTU/hr
(2.10kW)
480V input
7412 BTU/hr
(2.17kW)
600V input
4894 BTU/hr
(1.43kW)
Note
The heat output is higher while batteries are charging. Under normal operating
conditions, battery recharging periods are infrequent.