American Power Conversion 60kW InfraStruXureTM System Power Supply User Manual


 
InfraStruXure System—Installation and Start-Up 13
Installation Procedures
Level the PDU and NetShelter Enclosures
Leveling feet are attached under the enclosure at each corner. The leveling feet can help provide a
stable base if the selected floor space is uneven, but they are not intended to compensate for a badly
sloped surface. To level the enclosure:
1. Fit the 14-millimeter end of the open-ended wrench (provided) to the hex head just above the
round pad on the bottom of the leveling foot. Turn the wrench clockwise to extend the leveling
foot until it makes firm contact with the floor.
2. Repeat step 1 for each of the remaining leveling feet.
3. Use a level to determine which feet need further adjustment to level the enclosure. Adjust as
necessary.