American Power Conversion Bypass Static Switch User Manual


 
32 Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Battery Operation
During battery operation, the load is supported by the inverters. The inverters are supplied by battery
power, ensuring uninterrupted support to the load.
While the UPS is running in battery operation, a single-line diagram will appear on the screen with a
green line indicating the power flow from the batteries through the main inverter to the load for as
long as the batteries are energized.
CAUTION!
Do not open Q2, Q7 or Q8 when the UPS is in battery operation, as this action may result
in a load drop or a failure of the UPS to support the load.
Breaker Identification
Q1 UPS input breaker Q5 Static bypass input breaker
Q2 UPS output breaker Q7 Battery breaker 1
Q3 Manual bypass breaker Q8 Battery breaker 2
Note
Only operate a breaker when the associated breaker lamp is on.
Battery
Delta inverter Main inverter
Bypass Static Switch