American Power Conversion Bypass Static Switch User Manual


 
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 35
System Start-Up from Manual Bypass
Operation
If the UPS has been operating in manual bypass operation and no power is connected to the UPS, the
UPS display will be inactive. To re-start the system from manual bypass and achieve on-line
operation, close Q1 in the external maintenance bypass panel. This will power up the internal power
supply. Wait for the display to become active and follow the screen-prompted instructions.
CAUTION!
Follow these instructions carefully. Failure to do so could result in equipment damage.
Normal
5.40 PM
Operation
Startup
Shutdown
Network Configuration
User Configuration
View Event Log
Predictive Maintenance
Static Bypass Online
Online Static Bypass
Transfer from manual bypass to online
Transfer from online to manual bypass
Transfer from online to static bypass
Transfer from static bypass to online
Manual Bypass/Off
Normal
~~
Q7 Q8
Q2
Manual bypass/Off
0:00 AM
UPS Summary
Select Operation/
Configuration
Follow the start-up
instructions on the screen.
Active commands initially appear in
red. Once a command has been
carried out successfully, its text will
change to green. Important: After
pressing “Initiate charge” in step 2,
wait until the green lights go on
alongside battery breakers Q7 and
Q8 on front of the Battery Breaker
Box before closing the breakers.
Select Start-up
Normal
Manual bypass/Off
UPS Startup
5.40 PM
Close Q1
Close breaker Q5
Charge DC Capacitors
Close battery breakers Q7 and Q8
Close breaker Q2
Initiate transfer to static bypass
Open breaker Q3
Push UPS "ON" button
Display will be off until Q1 closed
SSW input
Initiate Charge
Connect battery
UPS output
Initiate transfer
Manual bypass
UPS will power up