American Power Conversion MX28B2400+27V Power Supply User Manual


 
Rev 1 MX28B-1200+27V PRODUCT MANUAL
41
Input Relay 4 {1}
[SYSTEM/IN-RLY/RLY-MAP]
An alarm activated in response to an external contact closure
or opening at the Input Relay 4 connection.
In-Rly 4 Alm m+
Ignore
OUTPUT RELAY SETUP
Output Relay 1 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Out-Rly 1 m+
Relay 1
Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Out-Rly 6 m+
Relay 6
Output Relay Minor Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Relay Minor m+
Minor
Output Relay Major Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Relay Major m+
Major
Output Relay 1 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Delay between sensing of the alarm condition and activation
of the alarm relay. An alarm condition must exist for longer
than the delay to be activated.
Out-Rly 1 Dly m+
0 sec
Output Relay 6 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Delay between sensing of the alarm condition and activation
of the alarm relay. An alarm condition must exist for longer
than the delay to be activated.
Out-Rly 6 Dly m+
0 sec
Output Relay Alarms
Output Relay 1 {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Output Relay 1 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays).
Out-Rly 1 Alm m+
Ignore
Output Relay 6 {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Output Relay 6 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays).
Out-Rly 6 Alm m+
Ignore
LVD SETUP
LVD1 Trip {1}
[MODULES/LVD/PARAM]
LVD1 trip (disconnect) threshold voltage.
LVD1 Trip m+
21.00 V
LVD1 Restore {1}
[MODULES/LVD/PARAM]
LVD1 restore (reconnect) threshold voltage.
LVD1 Reset m+
24.00 V
LVD2 Trip {1}
[MODULES/LVD/PARAM]
LVD2 trip (disconnect) threshold voltage.
LVD2 Trip m+
21.00 V
LVD2 Restore {1}
[MODULES/LVD/PARAM]
LVD2 restore (reconnect) threshold voltage.
LVD2 Reset m+
24.00 V