American Power Conversion MX28B2400+27V Power Supply User Manual


 
MX28B-1200+27V PRODUCT MANUAL Rev 1
22
5.9 Battery Temperature Probe Installation
The optional temperature probe is used to monitor the battery string temperature. To get the most
representative temperature measurement, the probe should be placed in contact with a battery cell that
is centrally located. The probe should be placed directly in contact with the cell (not the frame
surrounding the cell). Generally, the cell cover can be used; be careful not to allow the probe body to
touch the terminals.
1) Plug the connector end of the temperature probe into J5 on the left side of the control unit
backplane card in the base power bay.
2) Route the cable as required to position the probe on the selected battery cell
3) Remove the adhesive protection strip from the probe body and press the adhesive side of the
probe on the battery cell cover.
Figure 5-10 J5 Location
5.10 Power-Up and Checkout
Before initiating power-up and checkout, ensure that the following conditions exist:
1) Make sure that the external circuit breaker or fused disconnect protecting the cables from the
battery to the power plant is turned OFF (the battery cables should be connected to the power
plant, but the battery should not be connected).
2) Make sure that all load circuit breakers are turned OFF and all load distribution fuses are
removed.
3) Verify that all rectifiers have been installed.
4) Verify that converters if installed are set to ON and have their respective breakers ON.
J5