American Power Conversion MX28B2400+27V Power Supply User Manual


 
Rev 1 MX28B-1200+27V PRODUCT MANUAL
39
(Table 6-1. Parameter Locations, Descriptions, and Default Values)
PARAMETER DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Standby Alarm {1}
[MODULES/RECT/SET-ALM]
This alarm indicates that the control unit is holding a rectifier
in the standby mode.
Rect Stdby Almm+
n of N
Fan Fail Alarm {1}
[MODULES/RECT/SET-ALM]
This alarm indicates that a rectifier fan has failed.
Rect FF Alm m+
n of N
RFA Alarm {1}
[MODULES/RECT/SET-ALM]
This alarm indicates that a rectifier output has failed.
Rect RFA Alm m+
n of N
CONVERTER SETUP
Fail Safe Voltage {1}
[MODULES/CONV/PARAM]
Converter default output voltage if communication with the
control unit fails.
Conv Fail Safem+
-50.00 V
Communications Timeout {1}
[MODULES/CONV/PARAM]
The maximum converter communications response time
allowed before a communications failure is declared.
Conv Fail Commm+
1 min
Converter Information NOTE: This information can be viewed for each
converter installed by using the horizontal arrow keys.
Converter Current
[MODULES/CONV/INFO]
A display of the DC output current for the individual
Converter.
Conv 1 Curr #
7.9 A
Current Limit Alarm
[MODULES/CONV/INFO]
The status will be “ON” if the Converter has been forced into
its current limited mode.
Conv 1 CL #
OFF
Standby Alarm
[MODULES/CONV/INFO]
The status will be “ON” if the control unit is holding the
Converter in the standby mode.
Conv 1 Stdby #
OFF
Fan Fail Alarm
[MODULES/CONV/INFO]
The status will be “ON” if the Converter fan has failed.
Conv 1 FF #
OFF
Converter Fault Alarm (CFA)
[MODULES/CONV/INFO]
The status will be on if the Converter output has failed.
Conv 1 CFA #
OFF
Converter Alarms
Current Limit Alarm {1}
[MODULES/CONV/SET-ALM]
This alarm indicates that a converter has been forced into the
current limited mode.
Conv CL Alm m+
n of N
Standby Alarm {1}
[MODULES/CON/SET-ALM]
This alarm indicates that either the control unit is holding a
converter in the standby mode or an operator has set a
converter to standby
Conv Stdby Almm+
n of N
Fan Fail Alarm {1}
[MODULES/CON/SET-ALM]
This alarm indicates that a converter fan has failed.
Conv FF Alm m+
n of N
CFA Alarm {1}
[MODULES/CON/SET-ALM]
This alarm indicates that a converter output has failed.
Conv CFA Alm m+
n of N
CIRCUIT BREAKER SETUP
Breaker 1 Alias {1}
[MODULES/CIRBKR/ALIAS]
An alternate name (alias) that can be assigned to a circuit
breaker if desired.
Cir Bkr 1 m+
+24V