Each phase should be wired for a minimum of 15 A.
The rear cover of each Magnum VS shelf in the power system has two 1.125-inch (2.858 cm) diameter holes
for electrical conduit. Conduit can be run to each Magnum VS shelf, or, alternatively, strain relief is
provided for the direct installation of AC power cables. Please note that the ambient temperature and the
number of wires in a conduit must be considered in accordance with national and local wiring code
requirements (e.g., NEC).
AC Power Cord Sets
The AC power cord sets are not included with the Magnum VS DC System, and must be purchased
separately, or provided by the Licensed Electrician installing the system.
APC offers a standard AC input cable kit that includes two (2), 12 foot, 10 AWG, L6-30P power cords (SKU:
DCMOPTCS1).
WARNING: Hazardous ac voltage levels are present inside the power system. Keep the
rear cover in place when the system is operational or energized.