Output Voltage (factory
programmed)
54.0 Vdc
Operating Voltage Range 47 – 56.5 Vdc
Rated Output Current 100 A
Efficiency 85% Typical
Over Voltage Protection 59.5 Vdc
Output Current 90 A Minimum Continuous at 115 Vac Input
105 A Minimum Continuous at 230 Vac Input.
Current Limit 93 A Maximum at 115 Vac Input
110 A Maximum at 230 Vac Input.
Power Output per Rectifier @
54.5 Vdc
4900 W Continuous at 115 Vac Input
5700 W Continuous at 230 Vac Input
8.3. Controls and Indicators
TWF0500H54B Rectifier
Input Healthy LED AC power present.
Output Healthy LED DC output voltage between 39.5 to 59.5 Vdc.
Current Limit LED On when rectifier is in current limit.
Overvolts LED On when rectifier is above 57 Vdc. (Must be powered down to reset)
Magnum VS Controller
DC OK (Green) On when voltage is between 50 and 57 Vdc.
Major (Red) On when Major Relay is de-energized*
Minor (Yellow) On when Minor Relay is energized
Out Relay 1 (Red) On when Output Relay 1 is energized
(Flashing Green) Watchdog LED
* Major relay is energized in normal operation. If all power fails, major relay will lose power and the contacts