Magnum VS –48 Vdc User Manual Page 16
Circuit Breaker Protected Load Connections (30 or 60 A)
The circuit breaker lug landing connection provides a pair of #10-32 studs on 5/8” centers for mounting two-hole
lugs. A ring size of 6 mm may also be used. A right angle bus bar with two studs is provided to land the lugs.
Load Connections should be made as shown in. Cover connections with heat shrink after assembly.
Figure 2.8-1 Connections to Circuit Breakers
GMT Fuse-protected Load Connections
Connections for 1A to 14A loads require a ring terminal with a 0.170 in (4.3 mm) clearance hole and are located at
the rear of the unit. Load connections should be made as shown in Figure 2.8-2 and Figure 2.8-3.
Figure 2.8-2 Top Shelf GMT Fuse Connections
Load Returns
-54 Volt Load Connections