CAUTION:
To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel in a restricted-access
location, as defined by the NEC and IEC 60950, Third Edition, The Standard for Safety of
Information Technology Equipment.
Connect the equipment to a reliably grounded safety extra low voltage (SELV) source. An
SELV source is a secondary circuit that is designed so that normal and single fault
conditions do not cause the voltages to exceed a safe level (60 volts direct current).
The branch circuit overcurrent protection must be rated at a minimum of 5 amperes to a
maximum of 15 amperes.
Use 14 American Wire Gauge (AWG) or 2.5 mm2 copper conductor only, not exceeding
three meters in length.
Torque the wiring-terminal screws to 12 inch-pounds (1.4 newton-meters).
CAUTION:
The power-control button on the device does not turn off the electrical current supplied to
the device. The device might also have more than one connection to dc power. To remove
all electrical current from the device, ensure that all connections to dc power are
disconnected at the dc power input terminals.