Avaya S8500 Network Card User Manual


 
Using the Avaya Remote Supervisor Adapter
Viewing system health summary
Avaya Remote Supervisor Adapter User Guide 55
November 2003
Figure 27: System health temperature thresholds
The reported temperatures for system components are measured in the following ranges:
Warning Reset: If the temperature returns to a value below the warning reset value, the RSA
assumes that the temperature has returned to normal and does not generate any further alerts.
Warning: If the temperature reaches or exceeds the value specified for a warning, an alert is
generated.
Soft Shutdown: When the temperature reaches or exceeds the value specified for a soft
shutdown, a second temperature alert is sent and the RSA begins the shutdown of the S8500
Media Server. The shutdown will be an orderly operating-system shutdown. The S8500 Media
Server turns itself off when the shutdown completes.
Hard Shutdown: When the temperature reaches or exceeds the value specified for a hard
shutdown, the S8500 Media Server immediately shuts down. The RSA sends out an alarm to the
configured alert recipients.
Voltage thresholds
The RSA sends an alert if any monitored power source voltage falls outside the specified operational
ranges.
The voltages section displays the values RSA reacts to when reached or exceeded (see Figure 28, System
health voltage, on page 55). The values are not programable and cannot be changed.
Figure 28: System health voltage