6.0 UL Standard 1610 and
ULC S304 Intrusion
System Installations
To install the C900V2 to comply with UL Standard
1610 Applications (for Line Security, formerly
“Grade AA”) and ULC S304, you must satisfy all
requirements in this section.
6.1 Protected Premises Control
Panel without Digital Dialer
Backup
1. Use the D6200 Software to set the poll rate on
the C900V2. For UL approved installations, the
maximum interval is 90 seconds to meet the
requirement for polling supervision established
by UL. In most cases, to get a polling
supervision interval of 90 seconds, set the Poll
Rate to 75 and Retry to 13.
Because of differences in packet transmission
time latency within different networks, the poll
rate times vary. Contact Technical Support at
Bosch Security Systems, Inc. for assistance in
establishing the latency time for the network on
which you are installing the C900V2.
Refer to D6200 Software Operation and
Installation Guide (P/N: 4998154991).
2. Set DIP Switch 7 to the OFF position to enable
75-second supervision signals (the factory
default).
Refer to Table 5 on page 10 for the
functions of DIP Switches 5 through 9.
3. Add a telnet password to the communications
protocol of the C900V2 (refer to Section 4.5.3
Configuration Using Telnet, step 6, on
page 16). Retain this password for future
reference.
4. Program the control panel to send a daily test
signal through the digital dialer.
This tests the connection from the control
panel to the C900V2.
5. Connect Output 1 from the C900V2 to a
24-hour zone on the control panel.
This enables the control panel to locally
annunciate a C900V2 CPU failure.
6. Connect Output 2 from the C900V2 to a
24-hour zone on the control panel.
This enables the control panel to locally
annunciate a network failure.
You must use the C900V2 with a UL Listed
Burglary Alarm Control Unit or a UL Listed
combination Fire/Burglary Alarm Control
Unit with an integral or Listed digital alarm
communicator transmitter (DACT) installed
according to the manufacturer’s
instructions.
7. Install a tamper switch (such as a D110
Tamper Switch, available from Bosch Security
Systems, Inc.) on the control panel enclosure
and connect it to a 24-hour zone on the control
panel. If you use a separate enclosure for the
C900V2, install another tamper switch (D110)
on the enclosure and connect it to the same
24-hour zone.
8. Set DIP Switch 5 to OFF to disable Auto
Fallback.
9. Set DIP Switch 6 to ON to prevent fallback
caused by hang-ups.
Intercept errors are reported to the
receiver. If the receiver does not
acknowledge a signal sent that was
intercepted by the C900V2 in the
programmed time, the control panel
digital dialer hangs up and retries the
message transmission.
10. Set DIP Switch 9 to ON to enable Anti-
Substitution/Anti-Replay.
11. Set the shorting link on P3 to the H position.
Refer to Figure 12 on page 20 and Table 10 on
page 21 for the proper connection sequence.