2.2 Wiring
Figure 5: Wiring to a DS7400Xi in the Same Enclosure
3
1
7
5
4
10
8
2
9
6
1 – C900V2
2 – To LAN or WAN port
3 – DS7400Xi Control Panel
4 – Non-power limited area
NOTE: All power limited wiring must be at least
6.4 mm (0.25 in.) from the battery wiring.
5 – Battery
6 – EOL resistor for the control panel, attached to
terminals
7 – DS7481 Single Phone Line Monitor (optional)
8 – Telco jack
9 – RJ31X
10 – House telephone
You can use the C900V2 with a variety of control
panels. The next sections provide information for
wiring the C900V2 to a generic control panel. Refer
to Figure 5.
The control panel’s phone line monitor
becomes inactive when the C900V2
intercepts the phone line between the
telco service and the control panel. If
phone line monitoring is required, use an
external phone line monitor, such as the
Bosch Security Systems, Inc. DS7481.
The loss of a network connection closes
the Output 2 relay contact on the
C900V2. You can connect this output to
a 24-hour zone on the control panel.
The DS7400Xi is the only control panel
approved by UL to be wired in the same
enclosure as the C900V2. You must
install any other control panel in a
separate enclosure to receive the UL
approval.