System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
Page 13 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List of Parts
List GA: Distribution Cabinet
(20) GMT Fuse System Positions with
Split Bus
Features
♦ Single Voltage Distribution (-48V)
♦ Maximum Capacity: Input: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.
Total Distribution: 30A per bus, 60A total @ +65°C
Battery Recharge Current: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.
Battery Terminals as Remote Feed: 103A @ +40°C; 95A @ 50°C; 50A @ +65°C.
♦ (20) Mounting Positions for Alarm-Type Load Distribution Fuses, (10) per bus.
♦ Accepts GMT-Type Fuses (1/4A to 15A).
♦ Includes (20) dummy fuses equipped with safety fuse covers.
♦ Provides local and external fuse alarm.
♦ See Distribution Cabinet Electrical Connection Locations and Dimensions
.
Restrictions
Maximum distribution fuse size: 15A
Maximum size wire each fuse position accepts is 14 AWG.
Input is cable-fed only.
Maximum size wire input terminals accept is (1) 2 AWG per polarity.
No load or battery shunts are provided.
Ordering Notes
1) Order fuses, as required, per Tables 3
.