SAG582135000 System Application Guide
Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1)
Page 24 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Recm 90°C Wire Size
(1)
14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 2 AWG
Fuse/Circuit
Breaker
Amperage
Loop Length (feet)
(2)
1, 3, 5,
6, 10A
37
(3, 4, 5)
58
(3, 4, 5)
93
(3, 4, 5)
148
(3, 4, 5)
236
(3, 4, 5)
376
(3, 4, 5)
597
(3, 4, 5)
15A
24
(3, 4)
39
(3, 4, 5)
62
(3, 4, 5)
99
(3, 4, 5)
157
(3, 4, 5)
250
(3, 4, 5)
398
(3, 4, 5)
20A
-- 29
(3, 4)
46
(3, 4, 5)
74
(3, 4, 5)
118
(3, 4, 5)
188
(3, 4, 5)
298
(3, 4, 5)
25A
-- -- 37
(3, 4,)
59
(3, 4, 5)
94
(3, 4, 5)
150
(3, 4, 5)
239
(3, 4, 5)
30A
-- -- 31
(3, 4)
49
(3, 4, 5)
78
(3, 4, 5)
125
(3, 4, 5)
199
(3, 4, 5)
35A
-- -- -- 42
(3, 4)
67
(3, 4, 5)
107
(3, 4, 5)
170
(3, 4, 5)
40A
-- -- -- 37
(3, 4)
59
(3, 4, 5)
94
(3, 4, 5)
149
(3, 4, 5)
45A
-- -- -- 33
(3, 4)
52
(3, 4)
83
(3, 4)
132
(3, 4)
50A
-- -- -- 29
(3)
47
(3, 4,)
75
(3, 4)
119
(3, 4)
60A
-- -- -- -- 39
(3, 4)
62
(3, 4)
99
(3, 4)
70A
-- -- -- -- -- 53
(3, 4)
85
(3, 4)
75A
-- -- -- -- -- 50
(3, 4)
79
(3, 4)
80A
-- -- -- -- -- 47
(3)
74
(3, 4)
90A
-- -- -- -- -- -- 66
(3, 4)
100A
-- -- -- -- -- -- 59
(3, 4)
Recommended Crimp Lug
(6)
Load Lug
(1-hole)
245312200 245312400 245312400 245350400 245350600 245350700 245350800
Return Lug
(2-hole)
245342300 245342300 245342300 245390200 245346700 245346800 245346900
Table 4
Recommended Distribution (Load) Wire Size and Lug Selection for
TLS/TPS Fuse and Bullet Nose-Type Circuit Breaker (Load and Load Return)
Notes to Tables 4:
1
Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for wire rated
at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C, and 65°C was used. For
other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not
recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature.
Home