Emerson LXP48F1 Power Supply User Manual


 
System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
Page 27 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Maximum
Current
(Amps)
Ambient
Operating
Temperature
(1)
Loop
Length (Ft)
1.0 Volt Drop
(2)
Loop
Length (Ft)
0.25 Volt Drop
(2)
Recm 90°C
Wire Size
(1)
Recommended
Crimp Lug
(3)
163 40°C 36 9 (1) 2 AWG (1) 245350800
155 50°C 38 9 (1) 2 AWG (1) 245350800
110 65°C 54 13 (1) 2 AWG (1) 245350800
Table 5
Recommended Battery Wire Size and Lug Selection
Notes to Tables 5:
1
Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-17 (Single-Insulated
Copper Conductors in Free Air) for wire rated at 90°C conductor temperature operating in ambient
temperatures of 40°C, 50°C and 65°C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or
less, at rated full load output current of the shelf for the loop lengths shown in this column. Loop length is the
sum of the lengths of the positive and negative leads.
3
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information.