Installation
18
4.3.3 Removing the XDF from Skid
This unit is on casters—to prevent it from rolling, ensure that the skid is on a flat surface before
removing the XDF from the skid.
1. Remove eight lag bolts from the unit tie-down brackets on the controls side of the unit.
2. Remove the four tie-down brackets from the controls side of the unit (see Figure 15).
3. Find the ramps that were shipped with the unit.
4. Insert the two tabs on each ramp into the holes on the skid.
5. Remove eight lag bolts from the unit tie-down brackets on the side opposite the controls.
6. Remove the four tie-down brackets from the side opposite the controls.
Unit weight when empty is 710 lb (322kg). Weight may differ if optional equipment has been
installed. Refer to the packing slip for the unit’s exact weight.
7. Remove the XDF by rolling it off of the ramp using an appropriate number of personnel and
rigging based on the unit weight (see Figure 16).
Once off of the skid, the unit can be rolled to the installation site.
Figure 15 Remove lag bolts and brackets
NOTE
If the self-contained, air cooled XDF is too tall to pass through a doorway, the condenser fan
assembly may be removed, reducing the height by 2-1/2" (64mm).
Four (4) Lag Bolts and Two Brackets Per Corner
Right front corner detail
(controls side of XDF)