Emerson XDF Surge Protector User Manual


 
Specifications
50
Table 11 Electrical specifications
Electrical Data
Self- Contained,
Air Cooled XDF
Water/Glycol
Cooled XDF
Control & Fan Supply
Voltage 120 120
Ph 1 1
Hz 60 60
Unit FLA 8.3 5.0
Max Fuse or Circuit Breaker Amps 15 15
Min. Supply Circuit Ampacity 9.2 5.2
Receptacle required NEMA 5-15R NEMA 5-15R
Compressor Supply
Voltage 208 208
Ph 3 3
Hz 60 60
Unit FLA 15.7 15.7
Max Fuse or Circuit Breaker Amps 35 35
Min. Supply Circuit Ampacity 19.6 19.6
Receptacle required NEMA L21-30R NEMA L21-30R
Condensate Pump Amps (Optional) 0.72 0.72
Table 12 Total heat rejection
Rating Point,
Ambient
°F (°C)
Supply Air
Temperature,
°F (°C) Load, kW
Total Heat
Rejection, kW
95 (35) 77 (25) 14.1 20