FieldServer FS-8700-17 Computer Drive User Manual


 
FS-8700-17 Optomux Driver Manual
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 20
Read/
Write/
Both
COMMAND NAME OPTO22_FORMAT
OPTION
MASTER LENGTH
CONSIDERED (See
Notes)
NOTES
w
POWER UP CLEAR 4
w
RESET 4
w
SET TURN-AROUND DELAY 4
Uses 1 element of data array. Legal
values are 0,1,2,3
w
SET WATCHDOG DELAY 4
Uses 1 element of data array. Legal
values are 0 to 7
w
SET WATCHDOG DELAY (Analog) 3
Uses the 1st element of data array for
the timer value.
w
SET PROTOCOL 4
Uses 1 element of data array. Legal
values are 0,1
r
IDENTIFY Optomux TYPE 4
Polled data is stored in the 1st
element of the data array.
w
SET ENHANCED DIGITAL WATCHDOG 3
Delay is found in data array.
w
SET ENHANCED ANALOG WATCHDOG 1
Uses up to Length (max=16) array
elements. Module positions specified
get setup for fail values by using the
corresponding positions in data array.
w
SET TIMER RESOLUTION
Uses 1 element of data array.
w
SET TEMPERATURE PROBE TYPE 3
Temp probe type is found in first
element of data array
w
CONFIGURE POSITIONS 3
Non-zero module positions get set to
outputs. Zero module positions get
set to inputs
w
CONFIGURE AS INPUTS 3
Only module positions specified get
affected by command.
w
CONFIGURE AS OUTPUTS 3
Only module positions specified get
affected by command.
r
READ MODULE CONFIGURATION 4
w
WRITE OUTPUTS 1
Uses up to Length (max=16) array
elements. Non-zero elements get
turned on, zero value elements get
turned off.
w
ACTIVATE OUTPUTS 3
Only module positions specified get
affected by command.
w
DEACTIVATE OUTPUTS 3
Only module positions specified get
affected by command.
r
READ STATUS 1 2
If format=Bit then length is considered
during storage as bits are unpacked
into data array. If format is non equal
to bit then result is written as a single
value into one array element.
Retrieved data is stored in data array.
w
SET LATCH EDGES 3
Always affects all module positions.
Cannot be limited by length. Length is
only used when determining which
module positions are specified as
non-zero. Non-zero (Specified)
elements get set on->off, Zero (Non-