FieldServer FS-8700-17 Computer Drive User Manual


 
FS-8700-17 Optomux Driver Manual
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 1
1 Optomux Driver Description
The Optomux Driver allows the FieldServer to transfer data to and from devices over either
RS-232 or RS-485 using the Optomux Driver protocol.
The Optomux driver is a client only driver. This means that the driver can poll an
Optomux protocol compliant device but cannot emulate one.
The Optomux protocol provides a large command set. Many of the commands are used for
OPTO22 device configuration. This driver supports the full command set and thus the
driver may be used to configure as well as to poll OPTO22 devices.
1.1 Operating Methods
The Optomux driver provides three methods of operation. Users may use any
combination of methods.
Static Operation
If the hardware configuration is fixed and known then this is a suitable method. The
devices to be polled / commanded are configured using the FieldServer CSV file.
Dynamic Operation
If the hardware configuration may change or if hardware settings may change
dynamically or (more realistically) if you wish to change some aspect of the hardware
configuration such as a delay time or reset a latch without changing the CSV file and
resetting the FieldServer then this operating method is suitable. The commands set can
be configured by changing the values in the FieldServer’s data arrays. This operating
mode may be considered a data driven one.
Triggered Operation
This operating mode allows commands to be triggered by changing the value in the
FieldServer’s data arrays. This operating mode is useful if requiring an action triggered
by a remote device.
1.2 Statistics and Command Reponses
All FieldServer drivers report communication statistics that allow the operation of the
driver to be monitored.
In addition to the standard statistics, this driver exposes the communication statistics for
each port by presenting them in a user specified data array where they can be monitored
by a remote device or HMI system.
The Optomux driver also exposes the response status to each poll and command (if
required) by writing the response statuses to a user specified data array. This useful
feature allows remote devices to check whether a command has been completed
successfully.