FieldServer FS-8700-17 Computer Drive User Manual


 
FS-8700-17 Optomux Driver Manual
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 21
Read/
Write/
Both
COMMAND NAME OPTO22_FORMAT
OPTION
MASTER LENGTH
CONSIDERED (See
Notes)
NOTES
Specified) module positions get set
off->on
w
SET LATCH OFF TO ON 3
Only module positions specified get
affected by command.
w
SET LATCH ON TO OFF 3
Only module positions specified get
affected by command.
r
READ LATCHES 1 2
If format=Bit then length is considered
during storage as bits are unpacked
into data array. If format is non equal
to bit then result is written as a single
value into one array element.
b
READ AND CLEAR LATCHES 1 3,2
Non-zero (Specified) module
positions get affected (cleared) by
command. But all positions get read.
Read data get stored in data array.
During storage opto22_format is
considered. If format=bit then data is
unpacked and stored otherwise the
result for all 16 positions is stored as
one data element.
w
CLEAR LATCHES 3
Only module positions specified get
affected by command.
w
START/STOP COUNTERS 3
All positions are affected by
command. Non-zero (specified)
module positions start counting, zero
(unspecified) module positions stop
counting
w
START COUNTERS 3
Only module positions specified get
affected by command.
w
STOP COUNTERS 3
Only module positions specified get
affected by command.
r
READ COUNTERS 1
Data that is read is put into the
corresponding array elements of the
data array based on which module
positions are read.
b
READ AND CLEAR COUNTERS 1
Data that is read is put into the
corresponding array elements of the
data array based on which module
positions are read.
w
CLEAR COUNTERS 3
Only module positions specified get
affected by command.
w
SET TIME DELAY 3
The Modifier is specified in the CSV
file with the opto22_modifier1
parameter. The data (timeout) is
retrieved from the first element of the
data array.
w
INITIATE SQUARE WAVE 3
w
HIGH RESOLUTION SQUARE WAVE 3
w
RETRIGGER TIME DELAY 3
Only module positions specified get
affected by command.
w
GENERATE N PULSES 3
Only specified module positions get