FieldServer FS-8700-17 Computer Drive User Manual


 
FS-8700-17 Optomux Driver Manual
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 5
4.2 Client Side Connections
Section Title
Connections
Column Title Function Legal Values
Port Specify which port the device is
connected to the FieldServer
R1-R2, (FS-X40 Series)
R1 (FS-X20 Series)
Baud* Specify baud rate
110 – 115200, standard baud
rates only
At the time of publication of this
manual the OPTO22 device’s
support standard baud Rates in
the range 300-38400.
Parity* Specify parity Even, Odd, None, Mark, Space
Data_Bits* Specify data bits 7, 8
Stop_Bits* Specify stop bits
1
Protocol Specify protocol used Optomux
Handshaking* Specify hardware handshaking RTS, RTS/CTS, None
Poll Delay* Time between internal polls 0-32000 seconds
default 1 second
Example
// Client Side Connections
Connections
Port, Baud, Parity, Protocol, Handshaking, Poll_Delay
R1, 9600, None, Opto22 , None , 0.100s
4.3 Client Side Nodes
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric
characters
Node_ID OPTO22 device address. 0-255
Protocol Specify protocol used Optomux
Port Specify which port the device is
connected to the FieldServer
R1-R2, (P1-P8 with a
converter)
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port
Optomux1 , 1 , Optomux , R1