FieldServer FS-8700-17 Computer Drive User Manual


 
FS-8700-17 Optomux Driver Manual
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 22
Read/
Write/
Both
COMMAND NAME OPTO22_FORMAT
OPTION
MASTER LENGTH
CONSIDERED (See
Notes)
NOTES
affected. The Modifier (byte 1&2) are
specified in the CSV file with the
opto22_modifier1/2 parameters. The
data (number of pulses) is retrieved
from the 1st element of the data
array.
w
START ON PULSE 3
Only specified module positions get
affected. The data (period of pulses)
is retrieved from the 1st element of
the data array.
w
START OFF PULSE 3
Only specified module positions get
affected. The data (period of pulses)
is retrieved from the first element of
the data array.
w
SET TRIGGER POLARITY 3
All Module positions are affected by
this command. Non-zero (Specified)
module positions triggered by on,
zero module positions (un-specified)
elements get triggered by off.
w
TRIGGER ON POSITIVE 3
Only module positions specified get
affected by command.
w
TRIGGER ON NEGATIVE 3
Only module positions specified get
affected by command.
r
READ PULSE COMPLETE BITS 1 2
If format=Bit then length is considered
during storage as bits are unpacked
into data array. If format is non equal
to bit then result is written as a single
value into one array element.
Retrieved data is stored in standard
data array.
r
READ DURATION COUNTERS 3
Only specified module positions get
read. Data read gets put in
corresponding positions of data array.
b
READ AND CLEAR DURATION
COUNTERS
3
Only specified module positions get
read. Data read gets put in
corresponding positions of data array.
w
CLEAR DURATION COUNTERS 3
Only module positions specified get
affected by command.
w
WRITE ANALOG OUTPUTS 3
Only specified module positions get
written. Data written gets extracted
from corresponding positions of data
array.
r
READ ANALOG OUTPUTS 3
Only specified module positions get
read. Data read gets put in
corresponding positions of data array.
w
UPDATE ANALOG OUTPUTS 3
Only specified module positions get
written. Data written gets extracted
from corresponding positions of data
array.
r
READ ANALOG INPUTS 3
Only specified module positions get
read. Data read gets put in
corresponding positions of data array.