Figure 6: The telco alarm connector (DB-15 male)
Shelf manager command line interface (CLI)
You can use the shelf manager CLI to communicate with the intelligent management
controllers of the chassis, with boards in the chassis, and with the shelf manager itself.
The CLI is an IPMI-based set of commands that can be accessed directly or through a
higher-level management application or a script. Using the CLI, you can access
information about the current state of the chassis including current board population,
current sensor values, threshold settings, recent events, and overall chassis health.
Connecting to the shelf manager CLI using a serial port
You can connect to the shelf manager CLI by connecting the console cable supplied with
your chassis to a management PC console port and to the appropriate shelf alarm panel
serial port. To connect to the primary shelf manager use Serial 1. To connect to the
secondary shelf manager use Serial 2.
Table 5: Telco alarm connector pin assignment
Pin Name Description
1 AMIR+ MinorReset+
2 AMIR- MinorReset-
3 AMAR+ MajorReset+
4 AMAR- MajorReset-
5 ACNO CriticalAlarm - NO
6 ACNC CriticalAlarm - NC
7 ACCOM CriticalAlarm - COM
8 AMINO MinorAlarm -NO
9 AMINC MinorAlarm - NC
10 AMINCOM MinorAlarm - COM
11 AMANO MajorAlarm - NO
12 AMANC MajorAlarm - NC
13 AMACOM MajorAlarm - COM
14 APRCO PwrAlarm - NO
15 APRCOM PwrAlarm - COM
Shield Shelf-GND Shelf Ground