7 Troubleshooting and tips
V CAUTION!
Follow the safety instructions in the chapter "Important notes" on
page 27.
If a fault occurs, try to correct it as described:
– in this chapter,
– in the chapters for the installed components,
– in the documentation for the connected devices,
– in the help systems of the individual programs used.
If you do not manage to correct the problem, proceed as follows:
Ê Make a note of the steps you have taken and the situation in which the fault
occurred. Also make a note of the error messages displayed.
Ê Switch off the defective server blade or the system.
Ê Contact customer service.
7.1 System power indicator does not light up
The system's power indicator (see figure 15 on page 63) does not light up after
you have switched on your system:
Power cable not connected correctly
Ê Make sure that the power cable is correctly connected to the system's power
supply units and to the socket strip of the rack (see section "Connecting the
system unit to the mains" on page 52).
Power supply overloaded
Ê Unplug the power cables from the insulated sockets of the power supply
units.
Ê Wait a few seconds and then plug the power cables back into the sockets.
Ê Switch on your system.