Fujitsu C122-E119EN Server User Manual


 
- A = Number of mounted SBs (1 to 4)
- B = Number of mounted IO Units (1 or 2)
- C = Number of mounted expansion power supply units (0 to 2)
*3 If the intake air temperature is high (but within the normal temperature range), the fan enters high-speed mode
even when operation is normal.
*4 Condensation is not permitted.
*5 The temperature requirements depend on the altitude at the installation site.
- Installation at 0 to 500 m (0 to 1640 ft.) above sea level: 5 to 35°C (41 to 95.0°F)
- Installation at 500 to 1000 m (1640 to 3281 ft.) above sea level: 5 to 34°C (41 to 93.2°F)
- Installation at 1000 to 1500 m (3281 to 4921 ft.) above sea level: 5 to 33°C (41 to 91.4°F)
- Installation at 1500 to 3000 m (4921 to 9843 ft.) above sea level: 5 to 30°C (41 to 86.0°F)
The altitude specifications for the installation site include an allowable margin of error of ±100 m.
*6 "Non-operating" refers to the condition where a device has been disconnected from the power supply and stored.
*7 The actual acoustic noise level depends on the listener's location and the rack mounting conditions.
*8 The noise and acoustic power levels depend on the ambient temperature.
*9 "Non-operating" refers to the installed device in the power-off state.
*10 This is the value during operation.
*11 This value is for a single input cable.
*12 This value is for a single device.
1.3.3 PCI_Box installation specifications
TABLE 1.4 PCI_Box installation specifications
Item Description
External dimensions
[mm (in.)]
Width 482 (18.98)
Depth (*1) 740 (29.13)
Height 175 (6.89)
Weight [kg (lb)] (*2) 35 (77)
Air conditioning
requirements
Maximum heat output [kJ/h (BTU/h)] 1,656 (1,570)
Exhaust air flow
[m
3
/min (ft
3
/min)]
(*3)
FAN at low speed (Low) 3 (106)
FAN at normal speed (Normal) 4 (141)
FAN at high speed (High) 5 (177)
Temperature and
humidity
requirements (*4)
Operating Temperature [°C (°F)] (*5)
Humidity [%RH] 20 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
Non-operating (*6) Temperature [°C (°F)] 0 to 50 (32 to 122)
Humidity [%RH] 8 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 1 Installation Information
9 C122-H004-07EN