CHAPTER 1 Installation Data
1.3 Installation Specifications
6
C122-H007-01EN
1.3 Installation Specifications
This section explains installation specification of each equipment.
1.3.1 Installation specifications (PRIMEQUEST 2400E)
TABLE 1.2 Installation Specifications (PRIMEQUEST 2400E)
Item
Contents
External
Dimensions
[mm(in.)]
Width
445(17.52)
Length(*1)
782(30.79)
Height
438(17.25) 10U
Mass [kg(lb)] (*2)
128(282)
Conditions for
Air
Conditioning
Maximum Calorific value
[kJ/h(BTU/h)]
Input
Voltage:
200V
Interruptible Power
Supply(*13)
11,887(11,266)
High efficiency Power
supply(*13)
11,805(11,189)
Input
Voltage:
100V
Interruptible Power
Supply(*13)
12,528(11,874)
Displacement
[m
3
/min(ft
3
/min)](*3)
Recommended Environmental
temperature
10(353)
Maximum
24(848)
Temperature and
Humidity Conditions(*4)
Operati
ng Time
Temperature[ºC(ºF)]
(*5)
Humidity[%RH]
20 to 80
Highest Wet bulb
Temperature[ºC(ºF)]
29(84.2)
Down
Time(*6
)
Temperature[ºC(ºF)]
0 to 50(32 to 122)
Humidity[%RH]
8 to 80
Highest Wet bulb
Temperature[ºC(ºF)]
29(84.2)
Noise[dB](*7,*8)
60
Acoustic power level[B](*8)
7.8
Permissible Vibration
[m/s
2
(gal)]
Operating Time(including waiting
time)
4.0(400)( synthetic
seismic wave)
Down time(*9)
10.0(1000)( synthetic
seismic wave)
Permissible dust level[mg/m
3
]
0.15
Power
Conditions
Input Voltage and Pulse number
200 to 240VAC±10%
100 to 120VAC±10%
1φ
Frequency and Fluctuation
50/60 Hz+2/-4%
Maximum Power
Consumption
/Apparent Power
Operating
time
Input
Voltage :
200 V
Interruptible
Power
Supply(*13)
4.17 kW/4.39 kVA
High efficiency
Power
supply(*13)
4.04 kW/4.25 kVA
Input
Voltage :
100 V
Interruptible
Power
Supply(*13)
4.42 kW/4.65 kVA
Standby time
0.079kW
Power Factor(*10)
0.95 or more
Inrush current[A][Rush time](*11)
20 or less
Leak current[mA](*12)
6.8 or less at 200V
3.5 or less at 100V
*1: Dimensions without protrusions (Dimensions including the front cover are 832mm(32.76in)).