2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box)
32
C122-H007-01EN
Number
Description
(1)
Free access floor
(2)
200 mm (9.8 in)
(3)
300 mm (11.8 in) or more
(4)
Recipient power distribution
Remarks
The above figure shows an example of 19-inch rack made by Fujitsu Limited mounted with the device.
2.6 Cutoff Characteristics of Distribution Panel (At the time
of connecting power distribution box)
At the time of connecting the distribution panel through power distribution box, protection should be
coordinated so that the breaker of the device (or power distribution box) trips before the breaker of the
distribution panel trips. Such protection should be maintained. Therefore, the distribution panel should have
the characteristic conditions shown in “TABLE 2.5 Characteristic Condition of Distribution Panel Breaker”.
It is necessary to use Distribution panel Breaker suitable to these conditions.
TABLE 2.5 Characteristic Condition of Distribution Panel Breaker
Power input Device Name
Breaker capacity of Distribution panel Breaker
For Japan/general
overseas/North America
For Europe
AC200 - 240 V
Power distribution box
30A
32A
Cutoff characteristic is Long-time delay type and the cutoff characteristic equivalent to D (IEC898or IN0641
part II) shown in “FIGURE 2.28 Characteristics of Breaker of Distribution Panel” or cutoff characteristics