Fujitsu C122-H007-01EN Server User Manual


 
CHAPTER 2 Connected Information
2.3 Power cable connection
25
C122-H007-01EN
2.3.2 Power Cables Connections (PRIMEQUEST 2800E/2800B)
This section shows the figure of input power of PRIMEQUEST 2800E/2800B.
Standard Configuration of 200 V (Single power feed and no Redundant Power Feed)
with Power Distribution Box Connection
It is necessary to arrange three PSUs, three FANUs, three power cables (200 V IEC60320 C20) and two
power distribution box (200 V IEC60320 C19×3type) for 200 V standard configuration.
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution
panel. See “2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box).”
FIGURE 2.18 200V Standard Configuration (single power feed and no redundant power feed) with Power
Distribution Box Connection
Number
Description
(1)
Power distribution box (200V C 19 3 type)