CHAPTER 2 Connected Information
2.3 Power cable connection
23
C122-H007-01EN
100 V Redundant Power Feed Configuration (Single power feed, Redundant Power
Feed)
It is necessary to arrange four PSUs, two FANUs and four power supply cables (100 V NEMA 5-15P) for
100V redundant power feed configuration (single power feed, redundant power feed).
FIGURE 2.14 100V Redundant Power Feed Configuration (Single power feed, Redundant Power Feed)
Number
Description
(1)
Distribution Panel AC100V AC#0system
Standard Configuration of 200 V (single power feed, no redundant power feed) with
Power Distribution Box Connection
It is necessary to arrange two PSUs, four FANUs, two power cables (200 V IEC60320 C20) and two power
distribution boxes (200 V IEC60320 C19×3type) for standard configuration of 200 V (single power feed, no
redundant power supply).
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution
panel. See “2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box).”
FIGURE 2.15 Standard Configuration of 200 V (single power feed, no redundant power feed) with Power
Distribution Box Connection
Number
Description
(1)
Power distribution box (200V C 19 3 type)