Fujitsu C122-H007-01EN Server User Manual


 
CHAPTER 1 Installation Data
1.3 Installation Specifications
12
C122-H007-01EN
1.3.4 Installation Specifications (PCI_Box)
TABLE 1.5 Installation Specifications (PCI_Box)
Item
Contents
Dimensions
[mm (in)]
Width
482 (18.98)
Depth
740 (29.13)
Length
175 (6.89) 4U
Mass [kg (lb)] (*2)
35 (77)
Conditions
for air
conditioner
Max. calorific value [kJ/h (BTU/h)]
1656 (1570)
Displacement [m3/min
(ft
3
/min)] (*3)
FAN low speed (Low)
3 (106)
FAN medium speed (Normal)
4 (141)
FAN high speed (High)
5 (177)
Temperature
and Humidity
condition (*4)
At time of
operation
Temperature [°C (°F)]]
(*5)
Humidity [%RH]]
20 to 80
Max wet bulb temperature [°C
(°F)]]
29 (84.2)
Downtime
(*6)
Temperature [°C (°F)]]
0 to 50 (32 to 122)
Humidity [%RH]]
8 to 80
Max wet bulb temperature [°C
(°F)]]
29 (84.2)
Noise [dB] (*7, *8)
(Included in
installation)
Acoustic power level [B] (*8)
(Included in
installation)
Permissibl
e Vibration
[m/s
2
(gal)]
At the time of operation (Including standby)
4.0 (400) (Composite
seismic wave)
Downtime (*9)
10.0 (1000)
(Composite seismic
wave)
Permissible dust level [mg/m
3
]
0.15
Power
Supply
conditions
Input voltage and source resultant pulse number
200 to 240 VAC±10 %
100 to 120 VAC±10 %
Frequency and fluctuating Range
50/60 Hz + 2/-4%
Max
power
consumpti
on /
apparent
power
At the time of
operation
Input voltage: 200 V
450W/475 VA
Input voltage: 100 V
460W/485 VA
Downtime
Input voltage: 200 V
10W/40VA
Input voltage: 100 V
10W/35 VA
Power factor (*10)
More than equal to
0.95
Inrush current [A] [Rush hours] (*11)
Less than or equal to
25
Leak current [mA] (*12)
Less than or equal to
3.5
*1: Dimensions without protrusions.
*2: Numeric value when each optional device is mounted for maximum number of options.
*3: If the device is overloaded or if abnormality is detected even though the recommended environmental
temperature is used, the FAN rotates at high-speed.
*4: Protect from condensation.
*5: Temperature condition changes according to the installation location above sea level.
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C
(41 to 95°F)
For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to
33°C (41 to 91.4°F)
For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to
31°C (41 to 87.8°F)
For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to
29°C (41 to 84.2°F)
Error of + 100m in the sea level settings of the location of installation is permissible.
*6: Downtime is the condition in which the device is packed and maintained.