CHAPTER 2 Connected Information
2.3 Power cable connection
27
C122-H007-01EN
200 V Dual Power Feed Configuration with Power Distribution Box Connection
It is necessary to arrange six PSUs, six power cables (200 V IEC60320 C20) and four power distribution
boxes (200 V IEC60320 C19×3type) for 200 V dual power feed configuration.
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution
panel. See “2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box).”
FIGURE 2.20 200 V Dual Power Feed Configuration with Power Distribution Box Connection
Number
Description
(1)
Power distribution box (200V C 19 3 type)
2.3.3 Power Cable Connections (PCI_Box)
This section shows the figure of input power of PCI_Box.
Remarks
While configuring redundant power feed and dual power feed in this device, configure the same power feed
to PCI_Box.
100 V Configuration (single power feed, no redundant power feed)
It is necessary to arrange PSU and power cable (100 V NEMA 5-15P) for 100 V configuration (Single power
feed, no redundant power feed).
FIGURE 2.21 100 V Configuration (Single power feed, no Redundant power feed)
Number
Description
(1)
Customer distribution panel AC 100V AC#0 system