Fujitsu C122-H007-01EN Server User Manual


 
CHAPTER 1 Installation Data
1.3 Installation Specifications
8
C122-H007-01EN
1.3.2 Installation Specifications (PRIMEQUEST 2800E)
TABLE 1.3 Installation Specifications (PRIMEQUEST 2800E)
Items
Contents
Dimensions
[mm (in.)]
Width
445(17.52)
Depth (*1)
782(30.79)
Length
438(17.25) 10U
Mass [kg (lb)] (*2)
150(331)
Conditions for
air conditioner
Max. calorific
value
[kJ/h (BTU/h)]
Interruptible power source
17,712(16,787)
High efficiency power supply (*13)
17,388(16,480)
Displacement
[m3/min (ft
3
/min)]
(*3)
Recommended environmental
temperature
12(424)
Max.
28(989)
Temperature and
Humidity
conditions (*4)
At the time
of operation
Temperature [°C (°F)]]
(*5)
Humidity [%RH]
20 to 80
Max wet bulb
temperature [°C (°F)]]
29 (84.2)
Downtime
(*6)
Temperature [°C (°F)]]
0 to 50 (32 to 122)
Humidity [%RH]
8 to 80
Max wet bulb
temperature [°C (°F)]]
29 (84.2)
Noise [dB] (*7, *8)
60
Acoustic power level [B] (*8)
7.8
Permissible
Vibration [m/s
2
(gal)]
At the time of operation (Including
standby)
4.0 (400) (Composite seismic
wave)
Downtime (*9)
10.0 (1000) (Composite
seismic wave)
Permissible dust level [mg/m
3
]
0.15
Power supply
conditions
Input voltage and source resultant pulse number
200 to 240 VAC±10 %
Frequency and fluctuating Range
50/60 Hz + 2/-4%
Max power
consumption /
apparent power
At the time
of operation
Interruptible power
source (*13)
6.11 kW/6.43 kVA
High efficiency power
supply (*13)
5.92 kW/6.23 kVA
Downtime
0.084 kW
Power factor (*10)
0.95 or more
Inrush current [A] [Rush hours] (*11)
20 or less
Leak current [mA] (*12)
6.9 or less
*1: Dimensions without protrusions (832 mm(32.76in) including front cover)
*2: Numeric value when each optional device is mounted for maximum number of options.
However, rail for mounting rack (5.7kg) and cable type are not included.
Mass as per the installation configuration can be calculated using formula as shown below.
Device mass = 78 + (11.1 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg]
A = Number of mounted SB (Minimum 1 to Maximum 4)
B= Number of mounted IOU (Minimum 1 to Maximum 4)
C= Number of mounted PSU (Minimum 2 to Maximum 6)
D= Number of mounted DU (Minimum 0 to Maximum 2)*3: There are cases when device is overloaded or
when abnormality is detected, FAN rotates at high-speed even if recommended environmental
temperature is used.
*4: Protect from condensation.
*5: Temperature condition changes according to the installation location above sea level.
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C
(41 to 95°F)
For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to
33°C (41 to 91.4°F)
For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to
31°C (41 to 87.8°F)