Chapter 3: Setting Up the Autoloader
www.gateway.com
Choosing a location
Choose a location that meets the following criteria:
■ Select a location that is flat, sturdy, level, and close to the host server. Do
not place the autoloader on the floor or other carpeted surfaces.
■ Cabinet (rack) requirements — EIA 310-D standard 19-inch cabinet with
2U of clearance
■ Room temperature — 50 to 95ºF (10 to 35ºC)
■ Power source — AC power voltage: 100-127 VAC; 200-240 VAC line
frequency: 50-60 Hz
■ Air quality — Minimal sources of particulate contamination. Avoid areas
near frequently used doors and walkways, stacks of supplies that collect
dust, printers, and smoke-filled rooms.
■ Humidity — 20 to 80% RH non-condensing
■ Clearance — Back: minimum of 6 inches (15.4 cm). Front: minimum of
12 inches (30.8 cm). Sides: minimum of 2 inches (5.08 cm).
Warning Do not place the autoloader on its side or upside down,
or stack items that weigh more than 33 lbs. (15 kg) on top
of the autoloader.
Important Locate the AC outlet on the back of the autoloader. The
power cord is the autoloader’s main AC disconnect device
and must be easily accessible at all times.
Warning Excessive dust and debris can damage tapes and tape
drives.
Important Save all the original packing materials, including the
accessory box, in case you need to ship or move the
autoloader at a later time.