Honeywell NETAXS-123 Network Hardware User Manual


 
Installing the NetAXS-123 Panels
Installation
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A 33
NetAXS-123 supports a variety of Wiegand reader models. Some readers have only one brown
wire for LED control; others have two possible LED control inputs--orange for the green LED
and brown for the red LED. RED is the normal state of the Reader LED operation. The LED
turns GREEN for two seconds after a valid card read. Although readers operate similarly, LED
control can vary, depending on the manufacturer. Therefore, your readers may require some
testing to identify the right LED wire when the reader uses Dual LED wires. If you are using
Dual Line LED control, it’s recommended that you try the ORANGE-colored wire for a
GREEN LED.
The Reader Buzzer feature is not currently supported on the NetAXS-123 panels.
3.5 Wiring Door Strikes
Follow these steps to wire the door strikes to the Controller and Add-On Boards:
1. Use the following figure to locate the door strike terminals on the board.