Honeywell NETAXS-123 Network Hardware User Manual


 
38 www.honeywell.com
Installing the NetAXS-123 Panels
Installation
Note: Address 0 is not a valid setting.
b. Both DIP Switch 8 and DIP Switch 9 need to be either ON or OFF to be properly
configured.
Table 9: NetAXS-123 SW2 DIP Switch Settings
S1
a
S2
a
Selection
OFF OFF RS-485_2 termination (EOL) DISABLED
ON ON RS-485_2 termination (EOL) ENABLED (FUTURE) (Default)
a. Both DIP Switch 1 and DIP Switch 2 need to be either ON or OFF to be properly
configured.
Note: When you use the DIP switches to reset a panel to the original factory default
values, the Event History is lost and any customized databases are removed, so the
panel is reset with the original factory default database. This does not affect the
Ethernet IP address.
You can also use this ASCII command:
_I=pn_R
This command resets the panel to the original factory default values, but it only
removes the customized databases and restores the original factory default
database. The Event History is retained.
To reset the panel to the factory default values:
1. Make a note of the existing settings on SW1 DIP switches.
2. While the panel is powered up, turn all DIP switches to the OFF position.
3. Power down, then power the panel back up.
4. Wait for the panel to come up. The RUN LED should flicker fast.
5. Set the DIP switches back to their original positions.
6. Power down, then power the panel back up.
7. After the the panel comes up, the RUN LED should flash normal.
The panel is now reset to the original factory default values.