Liebert PDUTM Power Supply User Manual


 
Event Message Help Text
122
S2 SCR OPEN
Source 2 SCR Open.
One or more SCRs on Source 2 is open. Transferring between sources has been inhibited.
STS2/PDU output has been transferred to Source 1.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not
already full. This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
PRIMARY FAN FAIL
Primary Fan Failure
One of the primary cooling fans for the STS2/PDU has failed. The alternate fans are now running. The alter-
nate fans are not monitored.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
CONTROL MODULE FAIL
Control logic module has failed.
One of the control modules on the control board has failed.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.