Lucent Technologies 3000 VA Power Supply User Manual


 
Installation3
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
32
1 Place the conduit through the access hole on the junction box (see
Figure 10). Connect the exposed conduit wires to the corresponding
compression terminals (see the following table). Tighten the compression
terminals with a screwdriver.
2 Pivot the REPO receptacle guard out of the way, plug the REPO
plug/receptacle UPS connector into the REPO receptacle on the UPS rear
panel (see Figure 5 on page 26 or Figure 6 on page 27). Twist the
connector in place.
Mounting Holes
Plug/Receptacle
UPS Connector
Three Foot Cord
Terminal Block
Access Hole
for Conduit
Figure 10. REPO Cord Junction Box
Power Cable Terminations Tightening Torque
Wire Function Terminal
Position
Terminal Wire
Size Rating*
Entrelec Phoenix
Contact
REPO
L1 TB1Ć4
lb/
lb/
L2 TB1Ć5
12Ć22 AWG
(4Ć0 mm
2
)
3.5 - 5.3 lb/in 5.6 - 6.8 lb/in
Ground
TB1Ć6
()
*Suggested wire size is #18ĆAWG (0.75 mm
2
)75_C copper wire minimum.
NOTE: The REPO function activates when L1 and L2 are shorted together.