Lucent Technologies 3000 VA Power Supply User Manual


 
Installation 3
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
33
UPS with Bypass Module Startup
To start up the UPS:
1 Make sure the Bypass switch on the Bypass Module rear panel is in the
NORMAL position (see Figure 5 on page 26 or Figure 6 on page 27).
2 If your Bypass Module is a hardwired unit, supply utility power.
3 If your Bypass Module is a plug/receptacle unit, plug the input power cord
into the utility input connector on the Bypass Module rear panel.
Plug the other end of the power cord into a grounded, threeĆwire, AC
receptacle that has been wired in accordance with NEC specifications or
national wiring rules. (See Figure 11 for an example.)
L
N
G
Ground
Phase 1
Phase 2/Neutral
(International)
200/208/220/230/240V
Figure 11. L6Ć30 Receptacle
NOTE Steps 4 through 7 are for changing the output voltage. The output voltage is
factoryĆconfigured for 230V. If you do not need to change the output voltage, skip to
Step 8. Use the following table to select the correct output voltage according to your
Bypass Module.
Bypass Module Model Number UPS Voltage Selection*
60ĆHz BDM 208: 120/208 208
60ĆHz BDM 208: 120/240 208
60ĆHz BDM 208: 120 208
60ĆHz BDM 240: 120/240 Set to 220V for 110/220V BDM output
Set to 230V for 115/230V BDM output
Set to 240V for 120/240V BDM output
60ĆHz BDM 240: 120 Set to 220V for 110V BDM output
Set to 230V for 115V BDM output
Set to 240V for 120V BDM output
50ĆHz BIM 208 (Model 2500 only) 208
50ĆHz BIM 220 220
50ĆHz BIM 230 230
50ĆHz BIM 240 240
*The UPS output voltage should be set according to local mains voltage.