Lucent Technologies 3000 VA Power Supply User Manual


 
Communication5
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
48
UPS SERIAL COMMUNICATIONS MENU
SELECT OPERATION MODE
>
ENTER SELECTION > > >
1 CONTINUOUS DUMP
2
3
A
B
P
L
Z
Q
S
>
>
>
>
>
>
>
>
>
POLLED DUMP
SMART DUMP
ASCII TERMINAL
VT100 TERMINAL
PRINTER DUMP
LAN CONFIGURATION
SET BAUD RATE
QUIT WITHOUT SAVING NEW CONFIGURATION
SAVE AND RESTART
>D DISPLAY CONFIGURATION
4 Select a menu option by typing the corresponding letter or number key. All
menu selections are single keystrokes and are not caseĆsensitive.
D > Display Configuration displays the current communication settings and
the new settings that you have selected prior to saving them. The new
settings are not effective until you select save from the Main Menu.
Catalog # : D3023002202C
New COMM: ASCII
Press space bar to continue
Serial # :
Version #
COMM mode:
Baud x100:
LAN mode:
BP174C0998
3.05
Ser_Print
024
Novell
New Baud:
New LAN:
096
Novell
Site Fault Detection: Disabled
NOTE
Catalog #, Serial #, and Version # are all identification numbers unique to your
UPS and can also be found on the UPS nameplate.
1 > Continuous Dump The UPS regularly transmits status information to the
computer. Baud rates of 1200 to 2400 are recommended to reduce host
computer overhead when using this mode.
2 > Polled Dump Status information is transmitted only when requested by a
poll character (Control-E).
3 > Smart Dump Status information is transmitted when polled, as in the
previous mode. However, the transmission also occurs automatically
whenever UPS status changes. For example, if there is a power outage, UPS
status information changes and is therefore, automatically transmitted.
i