Lucent Technologies 3000 VA Power Supply User Manual


 
Communication 5
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
49
A > ASCII Terminal The UPS displays the formatted data on the attached
video terminal.
B > VT100 Terminal The UPS displays the formatted data on the attached
video terminal.
P > Printer Dump The UPS prints the formatted data on the attached printer.
L > LAN Configuration allows you to configure the UPS for a new LAN mode
and displays the Select LAN Configuration Menu.
SELECT LAN CONFIGURATION
1 > NOVELL
ENTER SELECTION >+>
2
3
4
Q
>
>
>
>
AS400
3-COM/LAN MANAGER
CUSTOM CONFIGURATION
TO QUIT THIS MENU
Select the AS400 option if you are using monitoring software to
monitor the UPS.
The Custom Configuration option has two screens: the first screen has
options available for inverter shutdown, and the second screen has
options available for the contact configuration. Consult your shutdown
software documentation for details on the required signal states for
configuring LAN communications.
A
>
Inverter shutdown control is enabled active HIGH (+12V)
SELECT CUSTOM LAN CONFIGURATION
ENTER SELECTION >=>
B
C
Q
>
>
>
TO QUIT THIS MENU
Inverter shutdown control is enabled active LOW (–12V)
Inverter shutdown control is disabled
Instructions: Choose the desired inverter shutdown function.
Warning: It is recommended that this feature should not be
used with normal RS-232 communications, conflicts may occur.